SIN.EQRTU1X

scritta PHASE OUT removebg little

This device is out of production and can no longer be ordered.
Alternative product to buy : SIN.EQRTUEVO1T

-------

RTU1X of the EQUOBOX system.

System for acquisition and storage of data from W.M-Bus 868 MHz / OMS EN13757 heat cost allocators and meters.
Through the web interface allows the reading of meters, the setup and the generation of reports, and the consultation of archived readings.
Integrated display for setup and reading data. Supports up to 500 meters of which max 250 wired (up to 20 meters wired via integrated M-Bus port).
Additional wired meters via SIN.EQLC1 and/or SIN.EQLC250. Power supply 24V AC/DC.

 

GENERAL CHARACTERISTICS

  • Master function for M-Bus cable/radio networks
  • Supports up to 500 meters of which max 250 wired
  • Support 20 on-board M-Bus devices
  • Expandable up to 250 devices by adding level converter modules in series (modularity 60/250 devices)
  • Possibility to extend the coverage radius via SIN.EQRPT868X
  • Removable antenna connector
  • Graphic display / Local memory up to 2 years 
  • 3 digital inputs, 2 relay outputs
  • Power supply 24V ac/dc or Power Over Ethernet
  • Meters/heat cost allocators/sensor query and data consultation via WEB interface
  • Ability to download reports on acquired data in CSV and Xls format
  • Email notification of events generated by digital inputs, counter status, threshold exceedance, etc.
  • Implementation of onboard relay outputs from the web interface, based on logic or in case of alarm
  • Removable via LAN, ADSL, or UMTS/GPRS router

 

ELECTRICAL CHARACTERISTICS

 

Power Supply

24Vdc +/- 10%, 24 Vac (min 20 Vac, max 40 Vac) or PoE (IEEE 802.3)

Installation category

Class II

Maximum consumption

7.5W

Ethernet N°2 (1 MAC): ETH1: Ethernet 1(PoE), ETH2: Ethernet 2
Fieldbus Total number of supported meters: 500 (wireless + wired)
Wired M-Bus interface max 20 meters
Wireless radio M-BUS interface
Digital Inputs N°3 - OFF=Vin<12Vdc, ON=Vin>12Vdc, max Vin=24vdc
Digital Outputs N°2 Relay, Contact load:
5A@30Vdc (Resistive Load)
2A@30Vdc (Inductive Load cosfi=0.4; L/R=7ms)
Auxiliary voltage for digital Inputs 15Vdcmax10mA


MECHANICAL CHARACTERISTICS

 

Temperature range

Operative:  -20°C a +55°C / Storage: -25°C a +65°C

Dimensions

90x71x62 mm (HxLxP) – DIN

Mounting

35mm DIN Rail (EN60715)

Protection Grade

IP20 (EN60529)


WIRED M-BUS INTERFACE

 

Reference standard

EN13757-2 (Physical Layer), EN13757-3 (Application Layer)

Baud rate

Min. 300bps – Max. 9600bps

Number of supported M-Bus meters

Without repeater M-Bus: 20, with repeater: max 250

Reading frequency

15 min / 60 min / 6 hours / 12 hours / 1 day

Recognition of collisions on M-Bus network        

Yes

Devices search/acquisition

Via Primary and Secondary Address


WIRELESS M-BUS INTERFACE

 

Reference standard

EN13757-4 (Physical Layer), EN13757-3 (Application Layer)

Frequency

868MHz

Number of supported W.M-Bus meters

500

Reading frequency

From 0 min to 24h                           

W.M-Bus Mode

S / T / C+T / S & C+T

Methods of meters recognition

Based on data reception or message reception SND_IR

DATA LOGGING

 

Data storage

1 year for intra-day data from wired meters,

2 months for intra-day data from radio meters

Reports

XLS or CSV format

Download report

Mail SMTP, FTP (Client), Webserver (report generation and downloading)

Report scheduling

Daily / Monthly / Two-monthly/ Three-monthly / Four-month / biannual / Yearly

USER INTERFACE

 

Display

Graphic, bright, 16 grayscale, multilanguage

Keyboard

6 tactile membrane key

Led Power

Operating status

HTTP

Multilanguage web server for data consulting and configuration


LOGICS / ALARMS/PLANNING

 

Alarm notification from M-Bus network

Anomalies /alarms meters, communication failure, thresholds violation

Onboard I/O

notification by e-mail of digital Inputs status

Logic

AND/OR based on local I/O

Thresholds violation (max value, min value, range, maximum consumption)

Planned actions

Local relay activation, sending of readings reports

Check the Presetting List for pre-set objects with the Equobox

SIN.EQLC1
M-Bus LEVEL CONVERTER 60 Dev.
SIN.EQRPT868X
Wireless M-Bus EXTENDER
SIN.EQLC250
M-Bus LEVEL CONVERTER 250 Dev.

WELCOME in SINAPSI's STORE !
We are SINAPSI, we are Italian and we have been passionately involved for almost 20 years in engineering, producing and distributing
devices and systems for monitoring consumption, energy and all sizes in the field.
Through our work we believe and want to generate savings, sustainability and give value to those who use our devices and contribute to a better world.