SIN.AL15W24VDCHD

DIN rail power supply, one DIN module size. Vout=24V DC, Iout=630mA Pout=15W

GENERAL FEATURES

  • Universal AC input/Full range
  • Protections: Short Circuit/Overload/Over voltage
  • Cooling by free air convection (working temperature: -30 ~ + 70 ° C)
  • Can be installed on DIN rail TS- 35/7.5 or 15
  • Isolation Class II 
  • LED indicator for power on
  • No-load power consumption <0.3W
  • 100% full load burn-in test
  • 1 year warranty
Login to add products to your cart

OUTPUT

DC Voltage

24 V

Rated current

0.63 A

Current range

0 ~ 0.63 A

Rated power

15.2 W

Ripple & Noise (max.) Note 2

150 mVp-p

Voltage Adj. range

21.6 ~ 29 V

Voltage tolerance Note 3

± 1.0%

Line regulation

± 1.0%

Load regulation

± 1.0%

Setup, rise time

2000 ms, 80ms/230VAC; 2000ms,80ms/115VAC at full load

Hold up time (Tip.)

30 ms/230VAC; 12ms/115VAC at full load


INPUT

Voltage Range

85 ~ 264 VAC ; 120 ~ 370 VDC

Frequency range

47 ~ 63 Hz

Efficiency (Typ.)

86%

Tensione AC (Typ.)

0.5 A / 115VAC ; 0.25 A / 230 VAC

Inrush current (Typ.)

cold start 25 A / 115VAC ; 45 A / 230 VAC


PROTECTION

Overload

110 ~ 145% rated output power;
Protection type: constant current limiting, recovers automatically after fault condition is removed

Overvoltage

30 ~ 36V Protection Type: Shut down o/p voltage, clamping by zener


ENVIRONMENT

Working temp.

-30 ~ +70°C (Ref. Derating curve)

Working humidity

20 ~ 90% RH non – condensing

Storage temp. humidity      

-40 ~ +85°C , 10~95% RH non – condensing

Temp. coefficient

±0.03%/°(0~50°C) RH non – condensing

Vibration

10~500Hz, 2G 10min./1cycle, period for 60 min. each long axes x,y,z

Mounting

Compliance to IEC60068-2-6

Operating altitude

2000 meters


SAFETY & EMC 
 NotE 4

Safety standards

UL60950-1, UL508, TUV EN61558-2-16, IEC60950-1 approved
Design refer to EN50178, tuv EN60950-1

Withstand voltage

I/P-0/P:3KVAC

Isolation resistance

I/P-O/P: 100M Ohms / 500VDC /25 °C / 70% RH

EMC emission

Compliance to EN55032 (CISPR32), EN61000-3-2-3 Class A, EN55024, EN55035, EN61000-6-2, EN61204-3

EMC immunity

Compliance to EN61000-4-2,3,4,5,6,8,11 Level 3,4 criteria A

OTHERS

MTBF

1166K HRS min. MIL-HDBK-217F (25°C)

DIMENSIONS

17,5*90*54,5mm (W*H*D)

PACKING

78g; 160pcs/13.5Kg/1.19CUFT

NOTE

  1. All parameters NOT specially mentioned are measured at 230VAC input rated load and 25°C of ambient temperature.

  2. Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1 uf & 47 uf parallel capacitor.

  3. Tolerance: includes set up tolerance, line regulation, and load regulation.

  4. The power supply is considered a component that will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.

  5. Constant current operation region is within 50% ~ 100% rated output voltage. The protection type for short circuit is hiccup mode and will recover automatically after the fault condition is removed.