RTU1T of the EQUOBOX system.
System for acquisition and storage of data from W.M-Bus 868 MHz / OMS EN13757 radio (through concentrators with Mesh Network technology) / cable.
Through a web interface, it allows the reading of the meters, the generation of reports, the setup, and the consultation of the archived readings.
Integrated display for setup and data reading. Supports up to 500 meters of which up to 250 wired (up to 20 meters cable via integrated M-Bus port).
Additional meters wired via SIN.EQLC1 and/or SIN.EQLC250. Power supply 24V AC/DC.
ELECTRICAL CHARACTERISTICS |
|
Power Supply |
24Vdc +/- 10%, 24 Vac (min 20 Vac, max 40 Vac) or PoE (IEEE 802.3) |
Installation category |
Class II |
Maximum consumption |
7.5W |
Ethernet Fieldbus
Digital Inputs Digital Outputs
Auxiliary voltage for digital Inputs |
N°2 (1 MAC): ETH1: Ethernet 1(PoE), ETH2: Ethernet 2 Total number of supported meters: 500 (wireless + wired) Wired M-BUS interface max 20 meters sinapsitech℗ radio interface N°3 - OFF=Vin<12Vdc, ON=Vin>12Vdc, max Vin=24vdc N°2Relays, Contact load: 5A@30V ac/dc (Resistive Load) 2A@30Vac/dc (Inductive Load cosfi=0.4; L/R=7ms) 15Vdcmax10mA |
|
|
Temperature range |
Operative: -20°C a +55°C / Storage: -25°C a +65°C |
Dimensions |
90x71x62 mm (HxLxP) – DIN |
Mounting |
35mmDINRail (EN60715) |
Protection Grade |
IP20 (EN60529) |
|
|
Reference standard |
EN13757-2 (Physical Layer), EN13757-3 (Application Layer) |
Baud rate |
Min. 300bps – Max. 9600bps |
Number of supported M-Bus meters |
Without repeater MBUS: 20, with repeater: max 250 |
Reading frequency |
15 min / 60 min / 6 hours / 12 hours / 1 day / 7 days/ 1 month |
Recognition of collisions on M-Bus network |
Yes |
Devices search/acquisition |
Via Primary and Secondary Address |
|
|
Frequency |
868MHz |
Number of the supported repeaters |
23 |
Supported application Layer |
Wireless M-Bus |
Methods of meters recognition |
Automatic or via import system file |
|
|
Data storage |
1 year for intra-day data from wired meters, 2 months for intra-day data from radio meters |
Reports |
XLS or CSV format |
Download report |
Mail SMTP, FTP (Client), Webserver (report generation and downloading) |
Report scheduling |
Daily / Monthly / Two-monthly/ Three-monthly / Four-month/ |
USER INTERFACE |
|
Display |
Graphic, bright, 16 grayscales, multilingual |
Keyboard |
6 tactile membrane keys |
Led Power |
Operating status |
HTTP |
Multilanguage web server for data consulting and configuration |
|
|
Alarm notification from M-Bus network |
Anomalies /alarms meters, communication failure, thresholds violation |
Onboard I/O |
notification by e-mail of digital Inputs status |
Logic |
AND/OR based on local I/O and M-Bus network Thresholds violation (max value, min value, range, maximum consumption) |
Planned actions |
Sending of readings reports |
Check the Presetting List for pre-set objects with the Equobox system
WELCOME in SINAPSI's STORE !
We are SINAPSI, we are Italian and we have been passionately involved for almost 20 years in engineering, producing and distributing
devices and systems for monitoring consumption, energy and all sizes in the field.
Through our work we believe and want to generate savings, sustainability and give value to those who use our devices and contribute to a better world.