Level Converter of the EQUOBOX system.
M-Bus level converter for managing up to 250 devices on the same M-Bus line. Field module for reading data from M-Bus meters.
Stand-alone module for use with SIN.EQSW1 (SIN.EQUSB232 must be provided) and/or third-party systems via RS232/RS485 ports (exclusive), M-Bus slave.
M-Bus slave interface for use as booster/repeater to extend the M-Bus network by a further 250 devices.
230V AC power supply (power supply included). Allows the power supply of n°1 external SIN.EQRTUxx units.
ELECTRICAL FEATURES |
|
Power supply |
110 ... 240 VAC, 47 ... 63 Hz through dedicated power supply included |
Installation category |
II Class as per EN 62368-1 |
Rated consumption |
6W + (0.07W * number of M-Bus slave) |
Maximum consumption |
45W, 45 VA Vout: DC 24V, max 15 VA |
|
|
Operating temperature range |
From -20°C to +55°C |
Storage Materials and colors |
From -25°C to +65°C PC+ASA, RAL9010 (white) |
Dimensions |
(2x) 110x71x62 mm (HxLxD) – including terminals |
Installation type |
35mm DIN bar (EN60715) |
Protection degree |
IP20 (EN60529) |
Connections |
110 ... 240 VAC power supply Functional Earth Vin LC/Vout LC: Power supply for level converter/repeater Vout 24 V DC (Max 15 VA) M-Bus Slave: to connect as a repeater/extender RS-485: connection for datalogger and software RS-232: connection for datalogger and software M-Bus Master: for connection to the M-Bus meter network |
Buttons |
Firmware update button |
M-BUS SECTION |
|
Reference standard |
EN13757-2 (Physical Layer) |
Baudrate |
Min. 300bps – Max. 9600bps |
Max number of M-Bus devices |
250 (≤ 1,5 mA) |
Max number of Repeater |
Up to 6 with parallel connection |
Voltage on the Bus |
39V |
Short circuit protection |
Yes |
Galvanic isolation |
Yes (See EN13757-2) |
Galvanic isolation M-Bus Master - M-Bus Slave |
Yes |
Echo Cancellation |
Yes |
Collision Detect with Break-Signalling |
Yes |
SIGNALING LEDs |
|
Run (Green Led) |
Operating status of the device |
TX M-Bus (Green Led) |
M-Bus Master transmission status |
RX M-Bus (Orange Led) |
M-Bus Master reception status |
Short Circuit (Red Led) |
Indicates short-circuit of the M-Bus Master line |
Overload (Orange) |
Indicates overload of the M-Bus Master line |
Power (Green Led) |
Indicates the correct power supply of the device |
|
|
Level Converter + QuickStart Guide |
0,166 Kg 0,055 kg |
Check the Presetting List for pre-set objects with the Equobox system
WELCOME in SINAPSI's STORE !
We are SINAPSI, we are Italian and we have been passionately involved for almost 20 years in engineering, producing and distributing
devices and systems for monitoring consumption, energy and all sizes in the field.
Through our work we believe and want to generate savings, sustainability and give value to those who use our devices and contribute to a better world.